Arc flash: what this service computes, and what it does not
An honest answer, because the part we skip is the part the label on the panel depends on.
What a study needs
An arc flash study under NFPA 70E rests on two numbers for every point in the system. The bolted fault current, which sets how much energy the arc can draw, and the clearing time of the protection upstream of that point, which sets how long it draws it. Incident energy follows from the two through the model in IEEE 1584.
What this service gives you
- Fault current in the IEC 60909 form, with the voltage factor you enter and every step shown.
- Clearing time of an inverse-time stage by IEC 60255-151, including a table across current multiples so you can see how the time moves as the fault point changes.
- A coordination chart that shows which stage clears first, because the clearing time that matters is the one of the device that actually operates.
What it does not compute
Incident energy and the arc flash boundary. The model is defined by IEEE 1584-2018, we do not hold that standard, and a number produced from a summary of it would be worse than no number: it ends up on a label that tells a person what to wear.
Nothing here replaces a study by a qualified engineer. Use these pages for the inputs and for checking someone else's arithmetic, not as the study itself.
If you need the whole study
Commercial packages do it end to end: EasyPower starts at $1,165 a year, ETAP and SKM PowerTools sit above that. They are worth it when you run studies regularly. When you need to check one number in someone else's report, the pages above cost nothing and show their work.