Arc flash: what this service computes, and what it does not

An honest answer, because the part we skip is the part the label on the panel depends on.

What a study needs

An arc flash study under NFPA 70E rests on two numbers for every point in the system. The bolted fault current, which sets how much energy the arc can draw, and the clearing time of the protection upstream of that point, which sets how long it draws it. Incident energy follows from the two through the model in IEEE 1584.

What this service gives you

What it does not compute

Incident energy and the arc flash boundary. The model is defined by IEEE 1584-2018, we do not hold that standard, and a number produced from a summary of it would be worse than no number: it ends up on a label that tells a person what to wear.

Nothing here replaces a study by a qualified engineer. Use these pages for the inputs and for checking someone else's arithmetic, not as the study itself.

If you need the whole study

Commercial packages do it end to end: EasyPower starts at $1,165 a year, ETAP and SKM PowerTools sit above that. They are worth it when you run studies regularly. When you need to check one number in someone else's report, the pages above cost nothing and show their work.