What you get
The initial symmetrical fault current and the line-to-line current, with the formula, the substitution and the source of every value. The voltage factor stays empty until you fill it.
Why two values exist for low voltage
Articles disagree about the low-voltage factor: some give 1.05, others 1.10. Both are right. Table 1 of IEC 60909-0 holds two rows for systems from 100 V to 1 000 V, and the choice follows the voltage tolerance of the system: 1.05 and 0.95 at ±6 %, 1.10 and 0.90 at ±10 %. Above 1 kV and up to 230 kV the factors are 1.10 and 1.00. Above 420 kV of highest equipment voltage the standard does not define them at all.
You can still enter your own
Pick a row and the factor fills itself, or type a value and it wins. A corporate method may set its own factor, and the calculation records which of the two the number came from.
What this is not
This page takes the impedance to the fault as given. Building that impedance from sources, transformers and lines is a separate job, and the Russian side of this site does it against Russian rules. For IEC work, bring your own impedance from the network model.