Irelay settings

Short-circuit current with a voltage factor

IEC 60909 form: the system voltage times the factor c, which you enter.

IEC 60909

The factor comes from the row you pick. Values checked against Table 1 of IEC 60909-0; verify them against your own copy before you sign the calculation.

Leave empty to use the row above, or enter your own value

Impedance to the fault

What you get

The initial symmetrical fault current and the line-to-line current, with the formula, the substitution and the source of every value. The voltage factor stays empty until you fill it.

Why two values exist for low voltage

Articles disagree about the low-voltage factor: some give 1.05, others 1.10. Both are right. Table 1 of IEC 60909-0 holds two rows for systems from 100 V to 1 000 V, and the choice follows the voltage tolerance of the system: 1.05 and 0.95 at ±6 %, 1.10 and 0.90 at ±10 %. Above 1 kV and up to 230 kV the factors are 1.10 and 1.00. Above 420 kV of highest equipment voltage the standard does not define them at all.

You can still enter your own

Pick a row and the factor fills itself, or type a value and it wins. A corporate method may set its own factor, and the calculation records which of the two the number came from.

What this is not

This page takes the impedance to the fault as given. Building that impedance from sources, transformers and lines is a separate job, and the Russian side of this site does it against Russian rules. For IEC work, bring your own impedance from the network model.