What you get
The trip time for your current and a table of times across multiples of the pickup, with the formula and its coefficients from IEC 60255-151.
The fields hold an example. Press Calculate.
Why the curve family matters more than the multiplier
The time multiplier scales the whole curve; the family changes its shape. A standard inverse stage and an extremely inverse stage with the same pickup and the same time at one point diverge by an order of magnitude at another, and that is where coordination breaks.
Below the pickup nothing happens
At a multiple of 1 the denominator turns to zero and the time goes to infinity. This calculator says the stage will not operate instead of printing a number, because a number there invites a coordination check that passes on nonsense.